LGM Products Ltd Unit 18 Riverside Industrial Park Dogflud Way Farnham Surrey GU9 7UG United Kingdom
Tel: +44 (0)1252 725257 Fax: +44
(0) 1252 727627 Email: sales@Lgmproducts.com
|

Duct Installed Smoke Detector
Uniguard UG-2 detects smoke in ventilation ducts using a unique single probe.
The UG-2 consists of a smoke detector, a single air sampling tube and a housing specially designed for optimum airflow through the smoke detector. The smoke detector is connected to the fire control panel.
Alternatively, the UG-2 is used in conjunction with control unit ABAV-S3 to control fire safety dampers, to avoid ventilation fans and to activate acoustic and optical alarms. The detector has a bayonet fitting to simplify mounting and removal. A contaminated detector will result in increased sensitivity and false alarms. To avoid nuisance alarms the detector has a service alarm (GREEN LED). This indicates that the detector should be cleaned.
|
|
Specification
| Detector Type |
Ionisation: UG-2-J Optical: UG-2-O |
| Operating Votlage |
Detector: 24Vdc from control unit Booster fan: 24Vac separate supply |
| Operating current |
Detector: 0.04mA Booster fan: 50mA |
| Service Alarm Current |
13mA |
| Fire alarm current |
55mA |
| Operating Temperature |
-20°C to +50°C |
| Maximum Humidity |
99% RH |
| Housing Material |
ABS |
| IP Rating |
IP54 |
| Weight |
800g |
| Air Sampling Tube |
0.6m, 1.5m or 2.8m |
| Airflow speeds |
0.2m/s to 20m/s |
Accessories
| Booster Fan |
M-UG 1 |
| Filter |
F1-UG (10 Pack) |
| Mounting bracket |
UG-Beslag |
| Insulated thermal housing |
UG-SH (IP65) |
| Countrol Units |
ABAV-S2 24Vac/Vdc ABAV-S3 230Vac |
|
|
|