LGM Products Ltd Unit 18 Riverside Industrial Park Dogflud Way Farnham Surrey GU9 7UG United Kingdom
Tel: +44 (0)1252 725257 Fax: +44
(0) 1252 727627 Email: sales@Lgmproducts.com
|

Analogue Heat Sensing Cable
- SKM-03 & SKM-03UK Controllers for conventional systems.
- SKM-95 Controller for Apollo XP95 addressable systems.
Key Features:
- Easy and economical to install.
- User friendly
- Controller will monitor up to 300m of sensor cable (dependant on ambient temperature).
- Temperature increases are detected in proportion to the length of the cable heated.
- The sensor cable is resistant to corrosion and moisture.
- Vds Approved.
- SKM-03/SKM-03UK for use with conventional fire panels.
- Loop powered SKM-95 controller for use with addressable fire panels (XP95 Series protocol).
- Cable can be reset after use.
|
|
How does it work?
The SKM heat sensing cable system provides early warning of an impending fire by detecting overheating in cable ducts, road tunnels, escalators, lift shafts, conveyor belts and similar difficult to monitor environments. The system uses 'Firesense' analogue heat sensing cable and the SKM-03 or SKM-95 controllers plus an end of line terminal box. The sensor cable is specially contructed coaxial cable. When the cable is heated there is a corresponding change in the electrical characteristics of the cable. This change is monitored by the controller and when sufficient causes an alarm. The controller constantly monitors for open and short circuit faults in the cable. Firesense cable may be physically heat tested any number of times, however, if it is destroyed by overheating or fire, the damaged section must be replaced.
|
SKM Controller Specifications
|
SKM-95 |
SKM-03 & SKM-03UK |
| Supply Voltage |
Loop powered |
24Vdc |
| Idle Current Consumption |
< 2mA |
28mA |
| Alarm current |
3.2 mA |
58 mA |
| Isolator Voltage |
<14V |
Not Applicable |
| Address Protocol |
XP95 series |
Not Applicable |
| 'FIRE' relay contact |
Not Applicable |
N/O Relay contact* |
| 'FAULT' relay contact |
Not Applicable |
N/C Relay contact* |
| Dimensions (W/H/D) |
105/105/65mm |
105/105/65mm |
| Weight |
270g |
270g |
| System Healthy LED indicator |
Green |
Green |
| Fire LED Indicator |
Red |
Red |
| Colour of housing |
grey, RAL 9002 |
grey, RAL 9002 |
| IP Rating |
IP65 |
IP65 |
*The SKM-03UK version is fitted with N/O-C-N/C relay contacts.
|

|
Firesense Cable Specification
| Coaxial construction |
Inner Core
Insulation
Braid
Outersheath
Options
|
Copper coated steel
Heat sensitive polymer
Tinned copper wire
Red coloured PVC
Rislan outer protective coating
Stainless steel braided
|
| Minimum Bend Radius |
6mm |
| Weight |
1.6kg per 100 metres |
| Operating temperature |
-20°C to +70°C |
| Alarm Temp. Range |
Complies with DIN/EN54-5 classes B & C
Typical example: Alarm initiated when 5 metres out of a total length of 300 metres of cable is heated to between 99°C to 115°C from an ambient of 20°C |
| Standard lengths |
100m, 500m, 1000m |
| Approvals |
Vds |
|
Accessories
A full range of cable fixings, junction boxes, intrinsically safe barriers and zone monitor panels are available. Please click here for more information.
|