LGM Products Ltd
Unit 18
Riverside Industrial Park
Dogflud Way
Farnham
Surrey
GU9 7UG
United Kingdom

Tel: +44 (0)1252 725257
Fax: +44 (0) 1252 727627
Email: sales@Lgmproducts.com




Analogue Heat Sensing Cable

The Firesense 2000 Linear Heat Detection Cable employs specially formulated polymers to provide a change in resistance with temperature that is monitored by the associated FS2000 controller. The insulation resistance of the coaxial cable falls when it is subjected to an increase in temperature and provides repeatable values at all levels up to the destruction temperature of the cable. This resistance change is monitored by the associated controller, which also provides a means of setting the alarm temperature of the cable. The Firesense 2000 cable is therefore ideal for detecting the early stages of fire and overheat conditions and may be physically tested any number of times by the application of heat.

Firesense 2000 Cable Specification

Construction Coaxial
Inner Core Copper Coated Steel
Insulation Heat sensitive polymer
Braid Tinned copper wire
Outer sheath Red PVC
Optional Rilsan outer protective coating (p/n 220083)
Minimum Bend Radius 6mm
Tensile Strength > 200N
Weight 1.6kg per 100 metres
Conductor Resistance Screen and score per 100 metres - 2 ohms
Operating Temperature -20°C to 70°C (short excursions to 200°C)
Typical Alarm Temp. Range 1 metre: 70°C to 125°
10 metres: 45°C to 100°C
NB Alarm temperatures may be set within limits at the associated controller.
The FS2000 Controller is designed to monitor Firesense 2000 Analogue Heat Sensing Cable and its associated end of line terminator for high temperature alarm and open and short circuit fault conditions. The unit may be directly connected on two cores to the zone input of a Fire Alarm Control Panel, alternatively it has the facility to operate from 24vdc and provide Fire and Fault relay contact. A dual-in-line switch is provided inside the unit to enable the user to set the controller for the length/alarm temperature of the associated cable.

NOTE: This controller and cable combination has not been tested to EN54 standard. Click here for an EN54 approved Heat Sensing Cable System.

Firesense 2000 Controller Specification

Part Number 115001
Enclosure Gray (RAL 7035) polycarbonate to IP65. Complete with hinged front secured with screws.
Operating Temperature -10° C to + 50°C
Dimensions (HxwxD) 180mm x 130mm x 75mm
Supply 24vdc from zone of conventional fire alarm panel or nominal 24 vdc for stand alone operation.
Current Consumption:
Quiescent 7mA
Alarm 35mA
Fault 35mA
LED Indicators: GREEN: System Healthy
YELLOW: Fault
RED: Fire
Controls Reset: Front panel membrane button
Lamp test: Internal Push Button
Alarm test: Internal Push Button
Cable Length Setting: Internal DIL switch
Outputs Two wires to first control panel
Control panel and end of line device terminals provided.
One set volt-free change over contacts for fire
One set volt free change over contacts for fault.
Terminals Two part connector suitable for 2.5mm² cable.
Cable entries 2 of PS13.5 IP65 glands
1 of PG7 IP65 gland (with inset for Firesense 2000 cable)
Weight 0.7kg
The End of Line unit provides an enclosure for terminating the Firesense 2000 Linear Heat Sensing Cable and also contains a sealed diode and resistor device. The end of the line unit returns the signal back to the controller for fire and fault monitoring.

Firesense 2000 EOL Unit Specification

Part Number 100637
Construction Grey (RAL 7035) Polycarbonate enclosure with front lid secured with screws.
Enclosure Rating IP65
Dimensions ((HxWxD) 78mmx100mmx52mm.
Operating Temperature -10°C to + 50°C
Input Firesense 2000 Analogue Heat Sensing Cable
Cable Entry 1 of PG7 IP65 gland
Weight 0.2kg


Accessories
A full range of cable fixings, junction boxes, intrinsically safe barriers and zone monitor panels are available. Please click here for more information.